HPM2.Z - an integrated set consisting of the external unit HPMO2 and the internal unit HPMI2 for...
HPM2.C
HPM2.C - Heat pump system consisting of the external unit HPMO2 and the internal 3in1 type HPMD unit for installation in new and renovated houses.
The HPM2.C system includes:
- external unit HPMO2
- internal "3in1" type HPMD unit
- external temperature sensors
- room temperature sensors
- 2 heating circuit sensors
Description
Installation diagram
Additional equipment
Technical data
Download
Download files
Product Details
Internal Unit HPMD 3in1
Combines the functions of (1) a hydraulic module with a system controller, (2) a domestic hot water tank, and (3) a heating buffer. Its compact design allows for easy installation.
- heat pump control panel
- contaminant separator
- circulation pump
- safety valve, electronic pressure gauge, automatic air vent
- electric heating unit
- three-way diverter valve
- remote control (C.MI2 module)
- compatible with other heat sources, e.g., gas boiler
- Amount of domestic hot water optimal for 3-5 people
- electronic anode (titanium)
- supports heat pump defrosting as well as room heating and cooling
- partition prevents mixing of hot supply water with cold water returning to the buffer
External Unit HPMO2
Inverter monoblock heat pump
- Energy class: A+++(35 °C)/A++ (55 °C)
- EVI injection system ensures high efficiency and water temperature up to 60°C
- Broad operating range at external air temperatures from -25°C to +43°C
- Quiet operation – sound pressure level at 1m distance: 41 to 51 dB(A) depending on the chosen device power - Q2 coefficient
- Planar room cooling or compatibility with fan coil units
- Condensate frost protection
- Smooth power modulation ensures optimal operation depending on heating needs:
- HPMO2-8: from 2.3 to 8.2kW (A7/W35)
- HPMO2-12: from 3.8 to 12.5kW (A7/W35)
- HPMO2-16/23: from 7 to 23kW (A7/W35)
Watch the video and learn about the KOSPEL heat pump heating system
Product Code | Description |
C.MI2 | The C.MI2 internet module allows remote control of the heat pump via the internet using a computer, tablet, or smartphone. Control is done through a web browser, providing easy and intuitive operation, as well as access to all advanced device control functions. |
HP.FF | Vibration isolation stand (base) for the heat pump 600x190x200 (2 pieces in the set). |
WE-019/01 | Temperature sensor for the storage tank / buffer. |
WE-019/05 | Temperature sensor for the heating circuits. |
HP.HS.24 | 24V humidity switch to protect against moisture accumulation. |
Product code | HPM2.C-8.1 | HPM2.C-12.1 | HPM2.C-16.1 |
---|---|---|---|
Energy Efficiency Class | A+++ (35 °C) / A++ (55 °C) | A+++ (35 °C) / A++ (55 °C) | A+++ (35 °C) / A++ (55 °C) |
Maximum Heating Power of the Heat Pump (kW) | 5,8 (A-7/W35) 7,1 (A+2/W35) 8,2 (A+7/W35) |
9,2 (A-7/W35) 11,3 (A+2/W35) 12,5 (A+7/W35) |
17,1 (A-7/W35) 20,5 (A+2/W35) 23,0 (A+7/W35) |
Efficiency Coefficient COP up to: | 4,6 (A+7/W35) 4,01 (A+2/W35) 3,49 (A-7/W35) |
4,75 (A+7/W35) 3,94 (A+2/W35) 3,37 (A-7/W35) |
4,76 (A+7/W35) 4,02 (A+2/W35) 3,47 (A-7/W35) |
Sound Power Level dB (A) | 49 | 55 | 59 |
Max Sound Pressure Level dB(A) - Coeff. Q2 | 41 from a distance of 1 meter | 47 from a distance of 1 meter | 51 from a distance of 1 meter |
Power Supply | 400 V 3N~ / 230 V~ | 400 V 3N~ / 230 V~ | 400 V 3N~~ |
Max Coolant Temperature | 60oC | 60oC | 60oC |
Nominal Current of the Overcurrent Circuit Breaker | 3x16A / 40A | 3 x 25 A / 50 A | 3 x 32A |
Min. Cross-Section of the Supply Cable | 5 x 2,5 mm2 / 3x6 mm2 | 5 x 2,5 mm2 / 3x6 mm2 | 5 x 2,5 mm2 |